Let’s explore how to plan a nurse call system for a new hospital in simple steps.
The best way to get a nurse call system right is before the plaster goes on the walls. Once the hospital is built and operational, every missed call point means knocking down walls, closing beds or resorting to workarounds. But in many projects, the nurse call system is not discussed until the electrical contractor is done.
This guide takes hospital owners, architects and project managers through planning a nurse call system from the drawing board through handover.
Start with the architectural drawings and mark all of the points where a patient may need assistance:
This gives you the true count of bed units and toilet units, which cost much more than the count of nurse stations.
Allocate individual nurse stations to individual beds. One common error is to connect an entire floor to one station when the floor is, in fact, operated as two separate wards. Each station should only show the beds to which it’s nurses are assigned.
Also decide whether calls should be repeated elsewhere, for example to a duty doctor’s room at night or to a supervisor’s display.
Read Also This: What Is a Wireless Nurse Calling System? A Complete Guide
For a new building, a wired system is generally the better choice, as cables can be run through conduits laid during construction. A wireless nurse call system is useful for blocks to be finished later, temporary wards or where the design changes late.
If you go for wired, give your electrical consultant cable routes and back-box positions early on so they are included in the electrical drawings rather than being added as an afterthought.
Not every place needs the same system. A reasonable divide is:
For critical areas, a station is much easier to manage with a model that has a large monitor display that can display many calls at once such as a ZX model nurse call setup.
In today’s wards, the bedside call unit is often located in the bed-head panel, alongside medical gas outlets, power sockets and lights. The panel supplier, medical gas contractor and nurse call supplier will need to coordinate cut-outs and positions. Toilet pull cords should be located where they can be reached from the floor and from the WC, not behind a door.
The nurse call system should be on a UPS or the hospital’s emergency power circuit so that it is still functional during a power failure, when patients are most anxious.
Ask suppliers to quote bed by bed, room by room, not as a lump sum. It makes it easy for comparing offers and to add beds later on. Break down by bed units, toilet units, door lights, central displays, hubs or repeaters, cabling and installation.
Test every single point at commissioning, not a sample:
Press every bed phone and pull every toilet cord
Finally, train the first batch of nurses on the system and agree a maintenance plan with the supplier for spare handsets and pull cords on site. A small cache of spares means a broken handset won’t leave a patient without a call point.
Nurse call systems are a small part of a hospital project but touch every patient every day. Planning it with the architecture, electrical and interiors avoids expensive rework and gives your nurses a system that works from day one.